Agrison Diesel Generators have become a necessity for those who require mobile power, back up power or simply just power. The consequences of a sudden loss of power, or no power at all, is not only inconvenient but can also be costly. Agrison offers a wide range of diesel generators of different sizes and kW to suit your needs. Our Diesel Generators are used in a variety of applications and have become a popular choice in the Australian and International market place. Do not be left in the dark, get yourself an Agrison Diesel Generator.

Product_Catalog_Icon

 

15 KVA Diesel Generators
ELECTRICAL
FREQUENCY
VOLTAGE
PRIME
STANDBY
50HZ 3 PH
415V/240V
15KVA/12KW
16.5KVA/13.2KW
Rated Speed
1500RMP-50HZ
Circuit Breaker
4 Poles
Power Factor
0.8–3 Phase
Current (A)
20.9
ALTERNATOR
Model
15KVA
Poles
4 poles
Winding Connections
star
Insulation
Class H
Enclosure
IP23
Exciter System
Self-regulating brushless
Voltage Regulator
AVR
Steady State Voltage Regulation
+/- 1.0%
Bearing
Single bearing sealed
Coupling
Flexible disc
Cooling
direct drive centrifugal blower fan
ENGINE
480D-14KW 50HZ
Output Rating KW 14KW
Model 480D
Fuel Diesel
Injection in-line
Aspiration Naturally Aspirated
Cylinders 4
Bore and Stroke MM 80*90
Displacement L 1.809
Cooling Water cooling
Engine Oil Specification SAE 3/11.5
Compression Ratio T.B.A
Engine Oil Capacity L 13
Governor Mechanical
Air Filter Dry Twin Stage
Fuel Consumption
100% Load Prime L/H 3.2 L/HR
75% Load Prime L/H 2.4 L/HR
50% Load Prime L/H 1.6 L/HR
STARTING SYSTEM
Starter Motor KW 12
Battery Capacity AH 80
Auxiliary Voltage V 12
FUEL SYSTEM
Fuel Tank Capacity H 8 -12 HOURS variable on load
WEIGHT AND DIMENSIONS – CANOPY
Length mm 1800
Width mm 800
Height mm 1120
Wet Weight(Standard Build) kg 680
Dry Weight(Standard Build) kg 750
Alarms and shutdown functions
High Coolant Temperature S
Low Oil Pressure S
Unexpected Shutdown A
Battery Charge Alternator Failure A
Over Speed S
Failure to Start A
Emergency Stop A
Alternator-high Frequency S
S-Shutdown A – Alarm